Feature for Truealarm Addressable Fire Alarm Control Panels
Brand :SIMPLEX
Approved : UL,ULC,CSFM, FM Approved
Product Onwer by TYCO
- 2 LCD Display, 2x 20 (40 Character) and LED for show the status information.
- Operationg by keypad and the panel LCD or via personel computer(PC),
- Upload/download PC pass RS232 for panel configuration and hevent istory log.
- INPUT
- Addresssble Device : can connect to up to 200 addressable True Aalrm detection points or addressable device point by using IDNet Commucation.
- OUTPUT
- Two NACs (Standard Notification Appliance Circuit) Class A or Class B output with solid dtate overcurrent protection per NAC each rated for 2 A.
- Selectale for SIMPLEX SmartSync two wire horn/strobe control or synchronized strobe control.
- Standard Power Supply
- Provide 3 A maximum @ nominal 24 DC
- Automatic input power selection operates with 120 VAC or 240VAC, 50 or 60 Hz.
- Battery charger for up to 12.7Ah battries in cabinet(UL and ULC) and UP TO 25 Ah bateries in seperate cabinet(UL only).
- Additional Standard Feature:
- Two Auxiliary relays
- NCAs, Relay output and communiccation circuit and power limited.
- Avaliable color are red and beige.
- UL Listed to standard 864.